4829 South 36th Street, Phoenix AZ 85040

WhisperWatt™ 600

Prime Rating: 480 kW (600 kVA)
Standby Rating: 528 kW (660 kVA)

60 Hertz

Standard Features

Download Product Brochure

DCA600SSV_rdax_200x127■ Heavy duty, 4-cycle direct injection, turbocharged, air-to-air intercooled diesel engine provides maximum reliability.
■ Brushless alternator reduces service and maintenance requirements and meets temperature rise standards for Class F insulation systems.
■ Open delta alternator design provides virtually unlimited excitation for maximum motor starting capability.
■ Automatic voltage regulator (AVR) provides precise regulation.
■ Electronic governor system maintains frequency to±0.25%.
■ Full load acceptance of standby nameplate rating in one step (NFPA 110, para 5-13.2.6).
■ Sound attenuated, weather resistant, steel housing provides operation at 74 dB(A) at 23 feet.  Fully lockable enclosure allows safe unattended operation.
■ Internal fuel tank with direct reading fuel gauges are standard.
■ E-Coat primer with polyurethane enamel finish coat.
■ Fuel/water separators remove condensation from fuel for extended engine life.
■ Simultaneous single and three phase power.
■ Battery switch

■ Complete engine analog instrumentation includes DC ammeter, oil pressure gauge, water temp. gauge, tachometer/hour meter, preheat indicator, manual engine speed control, emergency shutdown monitors, and emergency stop button.
■ Complete generator analog instrumentation includes voltage regulator control, ammeter phase selector switch, voltmeter phase selector switch, AC voltmeter, AC ammeter, frequency meter, panel light, and circuit breaker.
■ Automatic safety shutdown system monitors the water temperature, engine oil pressure,  overspeed, and overcrank. Warning lights indicate abnormal conditions.
■ Auto start/stop control allows generator to start automatically in the event of a commercial power failure.
■ Complete power panel.  Fully covered; three-phase terminals and single phase receptacles allow fast and convenient hookup for most applications including temporary power boxes, tools and lighting equipment.  All are NEMA standard.
■ Voltage change over board allows easy to change voltages as your applications require. 240/480 Buss Bar.
■ Low coolant level shutdown system provides protection from critically low coolant levels. Includes control panel warning light.
■ Emergency stop switch
■ EPA emissions certified – Tier 2 emissions compliant.